Three-phase Four-wire Cabinet-type Static Var Generator
GEYA Three-phase Four-wire Cabinet-type Static Var Generator,made in China, is a highly efficient solution for power factor correction and voltage stabilization. Perfect for industries that demand reliable and stable power, this static var generator optimizes energy use and enhances the overall efficiency of your system. Request a quote today and let our team help you find the ideal solution tailored to your needs.
The Three-Phase Four-Wire Cabinet-Type Static Var Generator (SVG) offers dynamic reactive power compensation and load balancing for three-phase four-wire electrical systems. Using DSP+CPLD digital control and a three-level topology, it provides precise and rapid compensation with a response time of less than 10ms. The cabinet design ensures robust protection and easy maintenance. Capacities range from 15kvar to 100kvar for 380V systems, addressing various three-phase application needs. This SVG also offers solutions for voltage imbalances in four-wire systems.
Model description:
GY
SVG
0.4
50K
/
4L
C
Enterprise code
Static var generator
Voltage level
0.22:220V
0.4:380V±20%
0.5:500V±20%
0.69:690V±20%
Rated Capacity (kvar) 5/15/35/50/75/100kvar
4L:Three-phase four-wire
C:Cabint
Features:
● Use DSP+CPLD all digital control core, three-level topology technology, advanced reactive power detection algorithm and PWM control strategy to achieve dynamic and accurate compensation of reactive power.
● Adopt modular design, which facilitates parallel connection of multiple modules, takes small space and is easy to maintain.
● The structural design of independent air ducts and independent warehouses ensures the stable operation of the equipment.
● Carry out full-range dynamic compensation for inductive reactive power and capacitive reactive power, and solve the three-phase unbalance problem at the same time.
● The dynamic response speed to the load is at the millisecond level, which can achieve dynamic and accurate compensation for the reactive power of impact loads.
Applications:
Three-Phase Four-Wire Cabinet-Type Static Var Generators are well-suited for applications requiring precise reactive power control and neutral current management in four-wire systems:
● Three-Phase Power Factor Correction (Four-Wire Systems): Improving power factor and reducing energy costs in three-phase systems with a neutral connection.
● Unbalanced Load Compensation: Mitigating the effects of unbalanced loads in four-wire systems, improving system stability and efficiency.
● Harmonic Mitigation: Reducing harmonic distortion in four-wire systems, protecting sensitive equipment and improving power quality.
● Data Centre Power Optimisation: Providing stable and clean power for data centres and other critical facilities utilising four-wire power distribution.
● Renewable Energy Integration: Supporting the integration of renewable energy sources by managing reactive power fluctuations and grid stability in four-wire systems.
Three-Phase Four-Wire Cabinet-Type Static Var Generators offer a comprehensive solution for optimising power quality and efficiency in three-phase four-wire electrical systems.
Technical Parameters:
220V series
380V series
500V series
690V series
Altitude
< 2000m, above 2000m, derate according to GB/T3859.2
Ambient temperature
-20~+50℃
Relative humidity
≤90%, no condensation on the surface when the monthly minimum temperature is 25℃
Pollution level
Level III below
Operating Voltage
AC220V±20%
AC380V±20%
AC500V±20%
AC690V±20%
Working frequency
50Hz±5%
Rated compensation capacity
5kvar
15/35/50/75/100kvar
90kvar
120kvar
Grid structure
L/N
3P3W/3P4W
Number of units connected in parallel
Ulimited
Overall machine efficiency
≥97%
On-off frequency
32kHz
16kHz
12.8kHz
12.8kHz
Function selection
Reactive power
Reactive po wer、Reactive po wer+imbalance
Reactive power compensation rate
≥99%
>95%
Full response time
<10ms
Noise
≤60dB
≤60dB
≤65dB
≤65dB
Control method
2-way RS485 interface (supports GPRS/WIFI)
Protection
Overload, software/hardware overcurrent, grid overvoltage and undervoltage, power failure, overtemperature, frequency abnormality protection, etc.
Overload, software/hardware overcurrent, grid overvoltage and undervoltage, grid voltage imbalance, power failure, overtemperature, frequency abnormality, shot circuit protection, etc.
Installation method
Rack/wall-mounted
Rack
Incoming line
Back incoming(rack type)、 upper incoming(wall-mounted)
Back incoming line
Protection level
IP20
Model& Specification:
Cabinet device model
Model Number
Compensation capacity (kvar)
System voltage (V)
Dimensions (D*W*H)
Cooling method
GY SVG-0.4-200k/4L-C
200
380±20%
800*1000*2200mm
Forced air cooling
GY SVG-0.4-250k/4L-C
250
380±20%
800*1000*2200mm
GY SVG-0.4-300k/4L-C
300
380±20%
800*1000*2200mm
GY SVG-0.4-400k/4L-C
400
380±20%
800*1000*2200mm
GY SVG-0.5-270k/4L-C
270
500±20%
800*1000*2200mm
GY SVG-0.69-360k/4L-C
360
690±20%
800*1000*2200mm
Hot Tags: Three-phase Four-wire Cabinet-type Static Var Generator
For inquiries about active harmonic filter, static var generator, power quality or price list, please leave your email to us and we will be in touch within 24 hours.