Three-phase three-wire Cabinet-type Static Var Generator
Introducing the Three-phase Three-wire Cabinet-type Static Var Generator – the ideal solution for power factor correction and voltage stabilization. Manufactured in China, this high-performance SVG is designed to optimize energy efficiency and ensure reliable power distribution for industrial applications. If you're looking to enhance the stability of your power systems, request a quote today!
The Three-Phase Three-Wire Cabinet-Type Static Var Generator (SVG) provides dynamic reactive power compensation for three-phase, three-wire electrical systems. It utilises advanced DSP+CPLD digital control and a three-level topology for accurate and fast-acting compensation, with a response time of under 10ms. The robust cabinet enclosure ensures safe and reliable operation in demanding industrial settings. Capacities range from 15kvar to 100kvar, catering to a variety of three-phase loads. This SVG is designed for 380V systems, offering effective power factor correction and voltage stabilisation.
Model description:
GY
SVG
0.4
50K
/
3L
C
Enterprise code
Static var generator
Voltage level
0.22:220V
0.4:380V±20%
0.5:500V±20%
0.69:690V±20%
Rated Capacity (kvar) 5/15/35/50/75/100kvar
3L:Three-phase three-wire
C:Cabint
Features:
● Use DSP+CPLD all digital control core, three-level topology technology, advanced reactive power detection algorithm and PWM control strategy to achieve dynamic and accurate compensation of reactive power.
● Adopt modular design, which facilitates parallel connection of multiple modules, takes small space and is easy to maintain.
● The structural design of independent air ducts and independent warehouses ensures the stable operation of the equipment.
● Carry out full-range dynamic compensation for inductive reactive power and capacitive reactive power, and solve the three-phase unbalance problem at the same time.
● The dynamic response speed to the load is at the millisecond level, which can achieve dynamic and accurate compensation for the reactive power of impact loads.
Applications:
Three-Phase Three-Wire Cabinet-Type Static Var Generators excel in industrial applications requiring precise reactive power management for three-wire systems:
● Three-Phase Power Factor Correction (Three-Wire Systems): Improving power factor in three-phase systems without a neutral connection, reducing energy costs and improving system efficiency.
● Three-Phase Motor Control (Three-Wire): Enhancing the performance and efficiency of three-phase motors in three-wire configurations.
● Industrial Power Stabilisation (Three-Phase Three-Wire): Stabilising voltage and ensuring consistent power quality in industrial settings using three-phase, three-wire power distribution.
● Manufacturing Process Optimisation: Improving the efficiency and stability of three-phase equipment and processes in manufacturing environments.
Three-Phase Three-Wire Cabinet-Type Static Var Generators offer a robust and effective way to manage power quality and optimise efficiency in three-phase, three-wire electrical systems.
Technical Parameters:
220V series
380V series
500V series
690V series
Altitude
< 2000m, above 2000m, derate according to GB/T3859.2
Ambient temperature
-20~+50℃
Relative humidity
≤90%, no condensation on the surface when the monthly minimum temperature is 25℃
Pollution level
Level III below
Operating Voltage
AC220V±20%
AC380V±20%
AC500V±20%
AC690V±20%
Working frequency
50Hz±5%
Rated compensation capacity
5kvar
15/35/50/75/100kvar
90kvar
120kvar
Grid structure
L/N
3P3W/3P4W
Number of units connected in parallel
Ulimited
Overall machine efficiency
≥97%
On-off frequency
32kHz
16kHz
12.8kHz
12.8kHz
Function selection
Reactive power
Reactive po wer、Reactive po wer+imbalance
Reactive power compensation rate
≥99%
>95%
Full response time
<10ms
Noise
≤60dB
≤60dB
≤65dB
≤65dB
Control method
2-way RS485 interface (supports GPRS/WIFI)
Protection
Overload, software/hardware overcurrent, grid overvoltage and undervoltage, power failure, overtemperature, frequency abnormality protection, etc.
Overload, software/hardware overcurrent, grid overvoltage and undervoltage, grid voltage imbalance, power failure, overtemperature, frequency abnormality, shot circuit protection, etc.
Installation method
Rack/wall-mounted
Rack
Incoming line
Back incoming(rack type)、 upper incoming(wall-mounted)
Back incoming line
Protection level
IP20
Model& Specification:
Cabinet device model
Model Number
Compensation capacity (kvar)
System voltage (V)
Dimensions (D*W*H)
Cooling method
GY SVG-0.4-200k/4L-C
200
380±20%
800*1000*2200mm
Forced air cooling
GY SVG-0.4-250k/4L-C
250
380±20%
800*1000*2200mm
GY SVG-0.4-300k/4L-C
300
380±20%
800*1000*2200mm
GY SVG-0.4-400k/4L-C
400
380±20%
800*1000*2200mm
GY SVG-0.5-270k/4L-C
270
500±20%
800*1000*2200mm
GY SVG-0.69-360k/4L-C
360
690±20%
800*1000*2200mm
Hot Tags: Three-phase three-wire Cabinet-type Static Var Generator
For inquiries about active harmonic filter, static var generator, power quality or price list, please leave your email to us and we will be in touch within 24 hours.