Introducing the 690V Rack Mount Static Var Generator – the ideal solution for efficient power factor correction and voltage regulation. If you're looking for reliable and high-performance equipment, request a quote today! Our advanced generator is designed to meet the needs of demanding industrial environments, ensuring stable power distribution and improved energy efficiency.
The 690V Rack Mount Static Var Generator (SVG) offers dynamic reactive power compensation for high-voltage, three-phase 690V electrical systems. It utilises advanced DSP+CPLD digital control and a three-level topology for precise and responsive compensation, with a full response time under 10ms. Designed for rack mounting, it provides convenient installation and maintenance in standard 19-inch racks. This SVG has a rated capacity of 120kvar, suitable for high-power industrial applications.
● Use DSP+CPLD all digital control core, three-level topology technology, advanced reactive power detection algorithm and PWM control strategy to achieve dynamic and accurate compensation of reactive power.
● Adopt modular design, which facilitates parallel connection of multiple modules, takes small space and is easy to maintain.
● The structural design of independent air ducts and independent warehouses ensures the stable operation of the equipment.
● Carry out full-range dynamic compensation for inductive reactive power and capacitive reactive power, and solve the three-phase unbalance problem at the same time.
● The dynamic response speed to the load is at the millisecond level, which can achieve dynamic and accurate compensation for the reactive power of impact loads.
Applications:
690V Rack Mount Static Var Generators are well-suited for high-voltage industrial environments requiring robust reactive power control:
● High-Voltage Power Factor Correction: Correcting power factor in 690V systems, reducing electricity costs and maximising the utilisation of existing electrical infrastructure.
● High-Voltage Motor Control: Improving the efficiency and performance of high-voltage motors in demanding industrial applications.
● Heavy Industrial Power Management (High-Voltage): Stabilising voltage and enhancing power quality in heavy industrial processes operating at 690V.
● Mining and Oil & Gas Applications: Providing reliable reactive power compensation in harsh environments often associated with mining and oil & gas operations.
690V Rack Mount Static Var Generators deliver a powerful and efficient solution for managing power quality and optimising efficiency in high-voltage industrial power systems.
Technical Parameters:
220V series
380V series
500V series
690V series
Altitude
< 2000m, above 2000m, derate according to GB/T3859.2
Ambient temperature
-20~+50℃
Relative humidity
≤90%, no condensation on the surface when the monthly minimum temperature is 25℃
Pollution level
Level III below
Operating Voltage
AC220V±20%
AC380V±20%
AC500V±20%
AC690V±20%
Working frequency
50Hz±5%
Rated compensation capacity
5kvar
15/35/50/75/100kvar
90kvar
120kvar
Grid structure
L/N
3P3W/3P4W
Number of units connected in parallel
Ulimited
Overall machine efficiency
≥97%
On-off frequency
32kHz
16kHz
12.8kHz
12.8kHz
Function selection
Reactive power
Reactive po wer、Reactive po wer+imbalance
Reactive power compensation rate
≥99%
>95%
Full response time
<10ms
Noise
≤60dB
≤60dB
≤65dB
≤65dB
Control method
2-way RS485 interface (supports GPRS/WIFI)
Protection
Overload, software/hardware overcurrent, grid overvoltage and undervoltage, power failure, overtemperature, frequency abnormality protection, etc.
Overload, software/hardware overcurrent, grid overvoltage and undervoltage, grid voltage imbalance, power failure, overtemperature, frequency abnormality, shot circuit protection, etc.
Installation method
Rack/wall-mounted
Rack
Incoming line
Back incoming(rack type)、 upper incoming(wall-mounted)
For inquiries about active harmonic filter, static var generator, power quality or price list, please leave your email to us and we will be in touch within 24 hours.
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies.