Need a reliable 500V Wall-mounted Static Var Generator? GEYA offers high-performance solutions with excellent precision and efficiency. For a customized solution, send us your inquiry today! We provide timely support, low maintenance, and exceptional service. Contact us now to boost your system’s performance and productivity!
The 500V Wall-Mounted Static Var Generator (SVG) offers dynamic reactive power compensation for three-phase 500V electrical systems. Using DSP+CPLD digital control and advanced three-level topology, the SVG delivers precise and rapid compensation, achieving a full response in under 10ms. Its modular design supports scalability, and the wall-mounted configuration saves valuable space. This SVG effectively addresses both inductive and capacitive reactive power imbalances, improving power factor and enhancing overall system stability. With a rated capacity of 90kvar, the 500V Wall-Mounted Static Var Generator provides a robust solution for demanding applications.
● Use DSP+CPLD all digital control core, three-level topology technology, advanced reactive power detection algorithm and PWM control strategy to achieve dynamic and accurate compensation of reactive power.
● Adopt modular design, which facilitates parallel connection of multiple modules, takes small space and is easy to maintain.
● The structural design of independent air ducts and independent warehouses ensures the stable operation of the equipment.
● Carry out full-range dynamic compensation for inductive reactive power and capacitive reactive power, and solve the three-phase unbalance problem at the same time.
● The dynamic response speed to the load is at the millisecond level, which can achieve dynamic and accurate compensation for the reactive power of impact loads.
Applications:
500V Wall-Mounted Static Var Generators are well-suited for optimising power quality in various high-voltage three-phase applications:
● Heavy Industrial Settings: Stabilising voltage and improving power factor in heavy industrial environments operating at 500V.
● High-Voltage Motor Drives: Compensating for reactive power fluctuations from high-voltage motors, improving motor efficiency and reducing energy consumption.
● 500V Power Distribution Systems: Enhancing power quality and stability in 500V distribution networks.
● Renewable Energy Integration (500V): Supporting grid stability and power quality in 500V systems integrating renewable energy sources.
500V Wall-Mounted Static Var Generators provide a reliable and efficient solution for managing reactive power and ensuring optimal performance in 500V three-phase electrical systems.
Technical Parameters:
220V series
380V series
500V series
690V series
Altitude
< 2000m, above 2000m, derate according to GB/T3859.2
Ambient temperature
-20~+50℃
Relative humidity
≤90%, no condensation on the surface when the monthly minimum temperature is 25℃
Pollution level
Level III below
Operating Voltage
AC220V±20%
AC380V±20%
AC500V±20%
AC690V±20%
Working frequency
50Hz±5%
Rated compensation capacity
5kvar
15/35/50/75/100kvar
90kvar
120kvar
Grid structure
L/N
3P3W/3P4W
Number of units connected in parallel
Ulimited
Overall machine efficiency
≥97%
On-off frequency
32kHz
16kHz
12.8kHz
12.8kHz
Function selection
Reactive power
Reactive po wer、Reactive po wer+imbalance
Reactive power compensation rate
≥99%
>95%
Full response time
<10ms
Noise
≤60dB
≤60dB
≤65dB
≤65dB
Control method
2-way RS485 interface (supports GPRS/WIFI)
Protection
Overload, software/hardware overcurrent, grid overvoltage and undervoltage, power failure, overtemperature, frequency abnormality protection, etc.
Overload, software/hardware overcurrent, grid overvoltage and undervoltage, grid voltage imbalance, power failure, overtemperature, frequency abnormality, shot circuit protection, etc.
Installation method
Rack/wall-mounted
Rack
Incoming line
Back incoming(rack type)、 upper incoming(wall-mounted)